SAREL SF6 Insulated Ring Main Unit - RMU
+.png)
RMSYS switchboard (Ring Main Unit - RMU) is composed by a stainless steel tank containing all the switching device and live parts: three position on-load switches (closed, open and earthed), vacuum circuit breaker or fuses for the protection of the transformer and/or outgoing lines.
A relief valve ensures the safety in the event of overpressure inside the container, in accordance with the standards IEC 62271-1.
A manometer placed on the front constantly monitors the internal pressure.
The switchboard is completed with a supporting metal structure divided into separate operating units.
Model :
~ RMSYS
|
Main electrical characteristics
|
|
Rated voltage
|
kV
|
12
|
24
|
|
Rated power-frequency withstand voltage 50Hz 1min
|
kV (r.m.s.)
|
28 (42)*
|
50 (75)*
|
|
Rated lightning impulse withstand voltage
|
kV (peak)
|
75 (95)*
|
125 (150)*
|
|
Rated frequency
|
Hz
|
50-60
|
|
Rated current main bus bars up to
|
A
|
630
|
|
Rated current functional units
|
A
|
630
|
|
Short-time withstand current
|
kA
|
20 - 3s
|
|
Peak value
|
kA
|
50
|
|
Withstand internal arc
|
kA
|
20 - 1s
|
|
Protection degree stainless steel tank
|
IP
|
67
|
◎ Download